Car Park Ventilation and Smoke Extract: Airflow, Jet Fans, Fan Rating

Author: Eng. Ahmed El-Tawil · Last reviewed:

An enclosed car park needs two ventilation duties: a normal rate that removes exhaust fumes (CO), and a higher smoke-extract rate in a fire. The normal rate is the larger of an airflow per floor area (0.75 cfm/ft², about 3.8 L/s per m², in IMC 2024 §404.1) and the air changes per hour required by the local code (commonly 6 ACH). Smoke extract is commonly 10 ACH, with fans rated to run at high temperature. Air is moved either through ducts or by ceiling jet fans.

Step 1 — the normal ventilation rate

Take the larger of:

Worked example (illustration): one basement level, 5,000 m², clear height 3 m → volume 15,000 m³.

Many car parks run the normal duty at reduced speed controlled by CO sensors, which saves a large share of the fan energy.

Step 2 — smoke extract

At 10 ACH (the smoke-clearance rate in the UK's Approved Document B and in the UAE Fire and Life Safety Code), the same basement needs 15,000 × 10 = 150,000 m³/h, usually split between two or more fans so one failure does not stop the system. Two-speed motors or variable speed drives let the same fans serve both duties.

Step 3 — make-up air

Codes that give a number set a minimum make-up rate for smoke mode: at least 85 % of the extract in the UAE Fire and Life Safety Code, and 80 % in Hong Kong's code of practice. Supplying somewhat less than is extracted also keeps the car park at a slight negative pressure, so fumes do not spread into the building. Make-up can come from ramps and openings or from supply fans.

Ducts or jet fans?

Ducted systemJet fans
Ceiling spaceLarge ducts across the ceilingSmall fans, no ducts
Main fansExtract and supplyExtract and supply at the ends
Design checkDuct calculationCFD simulation of air and smoke
Typical useLow ceilings with services, small car parksLarge open floors

Jet fans do not remove air themselves: they push air and smoke towards the main extract fans. The final number and layout must be checked by CFD — thrust per fan and coverage per fan from manufacturers' data are only a starting estimate.

The smoke-fan temperature class

A smoke extract fan must keep running while handling hot smoke. EN 12101-3 classifies fans by temperature and time (under the classification in force with EN 12101-3:2015: F300 = 300 °C for 60 minutes, F400 = 400 °C for 90 or 120 minutes). Since EU Regulation 2024/1681 other durations are possible at each temperature, so always write the duration with the class, for example F400 (400 °C, 120 min). What changes for a hot-gas fan:

A real temperature class requires a furnace test in a laboratory. Without a test report, the honest statement is "designed for … °C for … minutes — not tested".

Car park fans from HTC

HTC builds centrifugal and axial fans for car park ventilation and smoke extract to your calculated duty, with a performance datasheet, a 3D model and an Excel selection sheet. Performance is calculated and not tested, and smoke fans are stated as designed for the temperature, not furnace-tested — written on every datasheet. The factory's application module gives a preliminary estimate for pricing only; the system is designed by the project consultant.

Send the car park data (area, height, number of levels, ducts or jet fans, sprinklered or not, the code to follow) through the request form.

Code values are quoted with their source and must be confirmed against the edition adopted for your project. The example is an illustration, not a design.

Frequently asked questions

How much ventilation does an enclosed car park need?

For normal operation, the larger of a rate per floor area (0.75 cfm/ft², about 3.8 L/s per m², in IMC §404.1) and the air changes per hour required by the local code (commonly 6 ACH). Smoke extract usually needs a higher rate (commonly 10 ACH). Confirm with the local code.

What is a jet fan in a car park?

A jet fan is a ceiling-mounted fan that pushes air along the car park instead of ducts, driving air and smoke towards the extract points. The number and layout are checked by CFD.

Do car park smoke fans need a temperature rating?

Yes. Smoke extract fans must run at high temperature for a set time, for example the EN 12101-3 classes F300 or F400. A real class requires a furnace test in a laboratory.

Why is the make-up air less than the extract?

Supplying slightly less air than is extracted keeps the car park under negative pressure, so exhaust fumes and smoke do not spread into the building.

Have a project? Send the data through the request form.

Request a technical offer

Sources

  • UK Approved Document F volume 2 (2021) para 1.39: basement car parks, at least six air changes per hour as the alternative to a CO-based design; Approved Document B volume 2 para 11.5: designed to operate at 10 air changes per hour during a fire — gov.uk, read 28 Nov 2026
  • UAE Fire and Life Safety Code of Practice 2018, chapter 10 Tables 10.11 and 10.12: car park smoke purging at 10 air changes per hour, make-up air at least 85 % of extract; Hong Kong Fire Services Department Code of Practice 2022, 5.23 B.12: make-up air at least 80 % of extraction — read 28 Nov 2026
  • Commission Decision 2000/367/EC (consolidated 2011) and Delegated Regulation (EU) 2024/1681 Table 7.6: classes of powered smoke and heat exhaust ventilators — eur-lex.europa.eu, read 28 Nov 2026
  • ICC, Code Corner: 2024 IMC Chapter 4 Ventilation — IMC 2024 §404.1 Enclosed parking garages (https://www.iccsafe.org/building-safety-journal/bsj-technical/code-corner-2024-imc-chapter-4-ventilation, read 28 Nov 2026)
  • EN 12101-3 — Smoke and heat control systems: powered smoke and heat exhaust ventilators
  • Commission Decision 2003/629/EC, OJ L 218/54, 30.8.2003 — classes for powered smoke and heat exhaust ventilators (EN 12101-3): F200 120 min, F300 60, F400 90/120, F600 60, F842 30 (read 28 Nov 2026)
  • HTC engineering spec engineering/applications.md §1 and engineering/fans.md §8