Expansion Tank Sizing for Chilled Water Systems (Worked Example)

Author: Eng. Ahmed El-Tawil · Last reviewed:

A closed chilled water system needs an expansion tank because water expands as it warms — and in summer, when the plant is off, chilled water can warm by 35 °C or more. For a bladder (diaphragm) tank the ASHRAE equation is V_t = V_s · [(v2/v1 − 1) − 3α·Δt] / (1 − P1/P2), with P1 and P2 in absolute pressure. In a 10 m³ system going from 6 °C to 40 °C between 3 and 6 bar(g), the tank needs about 154 L of total volume.

The equation

V_t = V_s · [(v2/v1 − 1) − 3α · Δt] / (1 − P1/P2)

SymbolMeaning
V_tTotal tank volume
V_sWater volume of the whole system (pipes, coils, chiller, buffer tank)
v1, v2Specific volume of water at the lowest and highest temperature
αLinear expansion coefficient of the pipe material (steel 11.7 × 10⁻⁶ /K, ASHRAE)
ΔtHighest minus lowest temperature
P1Minimum pressure at the tank, absolute (fill pressure)
P2Maximum pressure at the tank, absolute (below the relief valve setting)

The term 3α·Δt is the growth in volume of the pipes themselves, which slightly offsets the water expansion.

The temperatures: the hot-climate trap

For chilled water the lowest temperature is the coldest the water gets in operation (for example 6 °C supply). The highest is not the return temperature — it is the temperature the water reaches when the plant is off, which is close to the ambient around the pipes. ASHRAE's summer design temperatures (0.4 % dry-bulb, 2021 data) run from about 36 °C in Amman and 39 °C in Cairo to 42 °C in Tripoli, 45 °C in Riyadh, 47 °C in Baghdad and 49 °C in Basra, and pipes on roofs get hotter still. Use the design climate of the site, not a value from a cooler country.

Worked example (illustration)

System volume 10 m³, lowest 6 °C, highest 40 °C, steel pipes, P1 = 3 bar(g), P2 = 6 bar(g).

  1. Densities: 999.94 kg/m³ at 6 °C, 992.22 kg/m³ at 40 °C → v2/v1 − 1 = 999.94 / 992.22 − 1 = 0.00778
  2. Pipe growth: 3 × 11.7 × 10⁻⁶ × 34 = 0.00119
  3. Net expansion: 0.00778 − 0.00119 = 0.00659
  4. Pressures absolute: P1 = 4.013 bar, P2 = 7.013 bar → 1 − P1/P2 = 0.428
  5. V_t = 10 × 0.00659 / 0.428 ≈ 0.154 m³ = 154 L → next standard size up.

Same system, highest temperature 50 °C: density 988.04 kg/m³ → net expansion 0.01050 → V_t ≈ 245 L. Ten degrees of ambient changes the tank by 60 %.

Practical points

Expansion tanks from HTC

HTC manufactures bladder and diaphragm expansion tanks to the volume and pressure you need, with a calculation note. The tanks are designed and fabricated to ASME VIII Division 1 rules — without ASME stamp and without third-party inspection. Every calculation note carries a signature box for the responsible engineer's review and approval, and every tank is hydrostatically tested with a test record.

Send the system data (water volume or pipe schedule, temperatures, fill pressure, relief setting) through the request form.

The equation and properties are quoted with their source; confirm the edition used for your project. The example is an illustration, not a design.

Frequently asked questions

Why does a chilled water system need an expansion tank?

Water expands when it warms. In a closed chilled water loop the water warms a lot when the plant is off in summer, and without a tank to absorb the extra volume the pressure rises until the relief valve opens.

Which temperatures do I use for a chilled water expansion tank?

The lowest is the coldest the water gets in operation (for example the chilled water supply). The highest is usually the ambient temperature the water reaches when the plant is shut down, which in hot climates can be 45–50 °C.

Why must the pressures be absolute?

The equation comes from the gas law for the air cushion behind the bladder, so P1 and P2 must be absolute pressures (gauge + about 1.013 bar).

What pre-charge should the tank have?

The air side is pre-charged to the minimum (fill) pressure at the tank connection, so the bladder holds no water until the system pressure rises.

Have a project? Send the data through the request form.

Request a technical offer

Sources

  • ASHRAE climatic design conditions 2021, 0.4 % cooling dry-bulb, station tables read through ashrae-meteo.info on 28 Nov 2026: Amman 36.1, Cairo 38.8, Tripoli 42.1, Riyadh 44.9, Baghdad 47.1, Basra 49.1 °C
  • ASHRAE Handbook — HVAC Systems and Equipment 2020 (SI), ch. 13 Eq. (15) and its variables (α = 11.7 × 10⁻⁶ /K for steel), read online for eng_constants expansion_formula / expansion_steel_alpha_per_k
  • Water density from CoolProp 8.1.0 (IAPWS-95) at 101.325 kPa: 999.94 kg/m³ at 6 °C, 992.22 at 40 °C, 988.04 at 50 °C (computed 28 Nov 2026)
  • ASME BPVC Section VIII Division 1 (vessel design rules)
  • HTC engineering spec engineering/tanks.md §2