Fire Dampers and Smoke Dampers Manufactured in Egypt to UL 555 Practices
HTC builds fire dampers, smoke dampers and combination fire/smoke dampers in Egypt, manufactured to UL 555 practices — not listed and not tested. That sentence is printed on every offer, drawing and nameplate, so the consultant and the approval authority know exactly what is being supplied.
Types
| Type | Description |
|---|---|
| Curtain | Interlocking blades folded above the opening, released by a fusible link (static) |
| Multi-blade with closing spring | Blades on shafts, closing spring and fusible link |
| Combination fire/smoke, motorized | Sealed multi-blade damper with spring-return actuator and thermal release |
| Smoke damper | Sealed multi-blade damper with actuator |
Design basis: 1½-hour rating, the rating the building code asks for where the wall or floor is rated less than 3 hours (IBC Table 717.3.2.1); fusible link 165 °F (≈ 74 °C), optional 212 °F (≈ 100 °C), above the code minimum of 160 °F.
A locked design, not a flexible one
Each type has a reference design with locked fields: frame and blade material and gauge, the smallest and largest single section, link type and rating, closing spring, sleeve gauge and length, retaining angles, expansion clearance, fixing method and spacing, permitted actuators, and mounting orientation. The factory's software refuses any request outside those limits — the size varies freely only between the stored minimum and maximum.
What ships with every damper
- A nameplate with model, size, rating, mounting orientation, serial number and status statement.
- Installation instructions for the contractor: opening, clearance, sleeve, retaining angles.
- A checklist: closing test by releasing the link, clearances, free movement.
Where this fits — and where it does not
Use these dampers where the project accepts a damper built to UL 555 practices without listing. Where the specification or the authority requires a listed and labelled damper, these dampers do not meet that requirement. A sample test programme is prepared; when a test report is registered, the statement will change to refer to the tested sample, within its limits only.
Where we supply
HTC manufactures in Egypt and supplies projects in Egypt. Export to Saudi Arabia, Libya, Jordan and Iraq is planned; send your enquiry and the factory will tell you what is possible today.
Head office: 73 Othman Ibn Affan Street, El Safir Square, Heliopolis, Cairo, Egypt.
How to order
Send the damper schedule through the request form: size, type, static or dynamic requirement, link temperature, vertical or horizontal mounting. Every request is reviewed by the factory before any reply.
Frequently asked questions
Have HTC fire dampers been tested to UL 555?
No. They are manufactured to UL 555 practices — not listed and not tested. This is written on every document and nameplate. If your project requires a listed damper, say so before ordering.
Which fire damper types are available?
Curtain type, multi-blade with closing spring, motorized combination fire/smoke dampers, and smoke dampers, on a 1.5-hour design basis.
Can I order a size or detail outside your design?
No. The factory's software refuses any size or detail outside the locked reference design of each type; there is no override.
Do you supply installation instructions?
Yes. Every fire damper ships with instructions for the opening, expansion clearance, sleeve and retaining angles, and a closing test in the inspection checklist.
Have a project? Send the data through the request form.
Request a technical offerSources
- International Building Code 2024, 717.3 (Table 717.3.2.1 damper rating; 717.3.2.2 smoke dampers Class I or II, 250 °F minimum; 717.3.3.1 link about 50 °F above duct temperature, not less than 160 °F) — ICC free viewer codes.iccsafe.org, read 28 Nov 2026
- NFPA 80 (2022) 19.5.1.1–19.5.1.2 and NFPA 105 (2022) 7.5.2.2, as reproduced in NFPA technical committee reports on nfpa.org, read 28 Nov 2026
- NFPA 90A 5.4.1–5.4.2 and 5.4.5.2 (damper rating; fusible link not less than 71 °C / 160 °F), as reproduced in NFPA committee reports, read 28 Nov 2026
- UL, Dampers: Marking and Application Guide (2025): hourly ratings, static and dynamic, leakage classes, actuators — ul.com, read 28 Nov 2026
- UL 555 — Fire Dampers
- UL 555S — Smoke Dampers
- NFPA 80, NFPA 90A, NFPA 105
- HTC engineering spec engineering/dampers.md, section B