Stairwell Pressurization: Pressure Limits, Door Force, Fan Sizing
A pressurized stairwell is kept at a slightly higher pressure than the floors around it, so smoke cannot enter the escape route. The design pressure has two limits: a minimum (NFPA 92: 12.5 Pa in a sprinklered building) so smoke is held back, and a maximum set by the door — NFPA 101 allows at most 133 N to set an egress door in motion. The fan is sized for the leakage through closed doors plus the air needed through the doors assumed open.
Step 1 — the minimum pressure difference
NFPA 92 (2021, Table 4.4.2.1.1) gives the minimum design pressure difference across the smoke barrier:
| Building | Minimum Δp |
|---|---|
| Sprinklered | 12.5 Pa (0.05 in. w.g.) |
| Non-sprinklered, ceiling 2.7 m | 25 Pa |
| Non-sprinklered, ceiling 4.6 m | 35 Pa |
| Non-sprinklered, ceiling 6.4 m | 45 Pa |
The local code may set different values — check it first.
Step 2 — the maximum pressure from the door
The force to open a door against the pressure is
F = F_dc + (W · A · Δp) / (2 · (W − d))
F_dc is the force to overcome the door closer, W the door width, A the door area, d the distance from the knob to the latch edge. With F limited to 133 N:
Δp_max = (133 − F_dc) · 2 · (W − d) / (W · A)
Worked example (illustration): door 0.9 × 2.1 m (A = 1.89 m²), d = 0.075 m, closer force 45 N (the value Klote uses, NISTIR 5132):
Δp_max = (133 − 45) × 2 × 0.825 / (0.9 × 1.89) ≈ 85 Pa.
A heavier closer leaves less room for pressure. The real closer force should be measured on site.
Step 3 — leakage through closed doors
Each gap behaves like an orifice:
Q = C · A_leak · √(2 · Δp / ρ), with C ≈ 0.65 (Klote gives 0.6 to 0.7 for door gaps) and ρ ≈ 1.2 kg/m³.
Worked example (illustration): 20 floors, one closed stair door per floor, leakage area assumed 0.02 m² per door, design Δp = 50 Pa:
Q per door = 0.65 × 0.02 × √(2 × 50 / 1.2) ≈ 0.119 m³/s
Total ≈ 2.37 m³/s ≈ 8,500 m³/h, before stair-wall leakage, open doors and margin.
The leakage area depends on the door type and how well it fits — use values from the consultant or measured on site, not the example.
Step 4 — open doors
When a door is open (firefighters, evacuation) the pressure across it collapses. Depending on the design basis, the system supplies a minimum air velocity through the open door(s). The number of doors assumed open and the velocity come from the code or method adopted (NFPA 92 performance design, or the European method of EN 12101-13:2022, which together with the new EN 12101-6 (kits) replaced EN 12101-6:2005).
Note for projects designed to the European standard: EN 12101-13:2022 §5.4.1 limits the opening force at the door handle to 100 N, on every floor including the fire floor — lower than the 133 N of NFPA 101. Use the limit of the standard your project follows.
Step 5 — tall buildings and stack effect
In tall buildings the temperature difference between inside and outside creates a pressure gradient over the height (stack effect). A single injection point at the top or bottom may over-pressurize one end and under-pressurize the other. Multiple injection points, or a supply shaft with dampers at several levels, keep the pressure even.
Step 6 — controlling the pressure
Doors opening and closing make the pressure swing. Two common solutions:
- Barometric relief damper that opens above a set pressure.
- Variable speed fan (VFD) controlled by differential pressure sensors.
Testing
Commissioning normally measures the pressure difference at every door with all doors closed, the force to open each door, and the conditions with the design number of doors open. Record the results door by door.
Pressurization fans from HTC
HTC builds centrifugal and axial fans for stair pressurization to the duty you calculate (airflow and pressure), with a performance datasheet, a 3D model and an Excel sheet of the selection. The performance is calculated and not yet tested — stated on every datasheet. The factory's application module gives a preliminary estimate for pricing only; the project consultant designs the system.
Send the stair data (floors, floor height, doors and their sizes, sprinklered or not, doors assumed open) through the request form.
All code values are quoted with edition and clause and must be confirmed against the edition adopted for your project. The examples are illustrations, not a design.
Frequently asked questions
What pressure should a pressurized stairwell hold?
At least the minimum in NFPA 92 (12.5 Pa in a sprinklered building, more without sprinklers), and low enough that the door can still be opened with no more than 133 N. The upper limit depends on the door size and its closer (about 85 Pa in the worked example below).
Why is there a maximum pressure?
Too much pressure holds the stair door shut. NFPA 101 limits the force needed to open an egress door to 133 N, so the pressure is limited by the door size and its closer.
How is the pressurization fan airflow calculated?
Add the leakage through all closed doors and the stair walls at the design pressure, plus the air needed through the doors assumed open, plus margin. Leakage through each gap is Q = C·A·√(2Δp/ρ).
Does every stairwell need a relief damper or a variable speed fan?
When doors open and close the pressure swings. A barometric relief damper or a fan on a variable speed drive with pressure sensing keeps it inside the allowed band.
Have a project? Send the data through the request form.
Request a technical offerSources
- NFPA 92 (2021) Table 4.4.2.1.1, as balloted in NFPA's Second Revisions report (F2020, SR-21) on nfpa.org: 12.5 Pa sprinklered; 25 / 35 / 45 Pa non-sprinklered at 2.7 / 4.6 / 6.4 m — read 28 Nov 2026
- NFPA 101 (2021 and later) 7.2.1.4.5.2, as reproduced in NFPA public-input reports, and IBC 2024 section 1010.1.3: 30 lbf (133 N) to set a door leaf in motion, 15 lbf (67 N) to open it to the required width — read 28 Nov 2026
- Klote and Fothergill, Design of Smoke Control Systems for Buildings, NBS Handbook 141 (NIST, 1983): Eq. 2.5 leakage flow with a flow coefficient of 0.6 to 0.7, Eq. 2.8 door opening force; the same door equation is IBC 2024 Eq. 9-1 — read 28 Nov 2026
- Klote, NISTIR 5132 (NIST 1993) §2: 45 N door-closer force on a 0.91 m door, and the 133 N of NFPA 101 quoted (https://nvlpubs.nist.gov/nistpubs/Legacy/IR/nistir5132.pdf)
- EN 12101-13:2022 — foreword ('This document together with EN 12101-6 supersedes EN 12101-6:2005'), §5.4.1 door opening force ≤ 100 N; EN 12101-6 is now 'Specification for pressure differential systems - Kits' (SIST EN 12101-13:2022 sample pages, read 28 Nov 2026)
- NFPA 92 — Standard for Smoke Control Systems, 2021 edition
- NFPA 101 — Life Safety Code, 2021 edition
- Klote, Milke, Turnbull, Kashef, Ferreira — Handbook of Smoke Control Engineering (ASHRAE)
- HTC engineering spec engineering/applications.md §2; eng_constants stair_dp_min_sprinklered, door_opening_force_max